Home Developers Evidence electrical.awg_to_mm

Public evidence

electrical.awg_to_mm

Machine-checked verification for calculation version 1.5.0 · tier engine_tested

CVP: CVP VERIFIED · CVP protocol 1.0.0-proposed · Engineering assurance · AWG geometry & calculation contract· CVP numerical verification covers AWG diameter/area geometry. Copper resistance is a 20 °C IACS material model. Ampacity is an educational code-context reference and is outside CVP golden numeric verification. · Protocol · Schema · Production report

Declared partition coverage
PASS · 5/5 declared partitions (geometry-formula, geometry-standard-nominal, copper-resistance-model, ampacity-reference-integrity, invalid-domain)
Versions
Calculation 1.5.0 · CVP protocol 1.0.0-proposed · Evidence 2026-09-10.wire-chart-claim-boundary
Verification revision
2026-09-10.wire-chart-claim-boundary · 5/5 property · digest 42bdfb24710d

Verification

Legacy regression suite: 46/46 calculation tests · Production surface contract 4/4

Three distinct suites: educational examples on the calculator page, this legacy regression count (46/46 golden + boundary), and the CVP verification suite below. They are not the same number. Property, metamorphic, round-trip, O3, and interface statuses/checks are recorded in the CVP Manifest . SKIP (0/0) means that suite has no published vectors.

    This calculator CURRENT · Public schema 1.5.0 matches · Semantic contract ✓ · Production attested · Public/cache ✓ · Origin ✓

CVP verification suite

Protocol checks from the Evidence Manifest. Distinct from the legacy regression suite above. Verification revision 2026-09-10.wire-chart-claim-boundary. Calculation version 1.5.0. CVP 1.0.0-proposed. 6/6 golden · 5/5 CVP boundary · 6/6 invalid · 5/5 property · 2/2 cross-interface · 1/1 CVP contract. digest 42bdfb24710d. CVP numerical verification covers AWG diameter/area geometry (unrounded formula + ASTM Table 1 identity). Copper resistance is a 20 °C IACS material model. Ampacity is an educational code-context reference and is outside CVP golden numeric verification.

  • Golden (oracle-backed) 6 / 6
  • CVP boundary 5 / 5
  • Invalid input 6 / 6
  • Property 5 / 5
  • Cross-interface 2 / 2
  • CVP contract 1 / 1
  • Interfaces PASS · UI (SSR) / REST / MCP
  • Interface claim ui-ssr is query-result HTML, not a live browser session. Human URL alias: /calc/wire/wire-gauge-chart?a=12&mode=awg-mm ≡ /calc/wire/awg-to-mm?awg=12&mode=awg-mm ≡ REST awg-to-mm and wire-gauge-chart ≡ MCP electrical.awg_to_mm.
  • Verified scope AWG geometry & calculation contract
  • Assurance Engineering
  • release artifacts aligned PASS
  • schema valid input executes PASS
  • engine success output validates schema PASS
  • schema rejects incomplete input PASS

Fingerprint sha256:912d7468eb9a95fd6550fce600bb84f727602ebc17f16b288e2b8a1c46d87493

Input schema sha256:871fc2ccfe8d3ea3aa8bbd7c74d37445f684f6926de3b69c4be5c80e5034648c · Output schema sha256:602cbe63d52662bc4b179c09784aa891368df1ab86d1592620fdd16166f94682 · Build-time SHA-256 digests prove published artifacts agree with each other (release_integrity.scope=workspace). Production attestation GETs canonical URLs twice (public/cached view and origin), including Capability HTML, via npm run attest:production --write (published at /.well-known/calculatorx-production-attestation.json) and fails if the public Capability page advertises a different calculation_version. This is artifact consistency, not an independent immutable release log.

Build & scope

Engine identity and declared limitations.

Tool
awg-to-mm
Engine
awg
Engine build
2026-09-10
Evidence core
2026-09-10T22:48:17.762Z
Rendered
2026-09-16T22:03:43.709Z
Last reviewed

Assumptions

  • Solid round conductor of the stated AWG; no insulation.
  • Standard AWG logarithmic definition with d₃₆ = 0.127 mm (ASTM B258-18(2026); 2026 reapproval of B258-18).
  • Copper resistance uses ρ = 1.7241×10⁻⁸ Ω·m at 20 °C (NBS Handbook 100 / 100% IACS annealed copper material model).
  • Ampacity is an educational NFPA 70–style thermal reference (table-like 310.16); edition not pinned; not jurisdiction-usable; not a branch-circuit/OCPD rating.

Limitations

  • Solid round conductor geometric model (ASTM B258-18(2026); 2026 reapproval of B258-18)
  • Primary geometry is unrounded geometric progression (formula_derived); ASTM Table 1 SI nominals are a separate standard_nominal track for integer 4/0–56
  • Not stranded equivalent area or insulated OD
  • Copper Ω/km is a 20 °C material model, not AWG geometry
  • Ampacity is an educational NFPA 70–style thermal reference (table-like 310.16, edition not pinned); copper 14–4/0 include 60/75/90 °C; 16 AWG and finer not tabulated; not jurisdiction-usable and not a branch-circuit rating
  • CVP numeric goldens cover AWG diameter/area geometry; resistance is a 20 °C IACS material model; ampacity is dataset-integrity only, not NEC compliance
  • Integer 4/0 (−3) through 56 = standard_range + formula_derived (+ standard_nominal); non-integer n in that span → AWG_NONSTANDARD_GAUGE + formula_interpolation; n outside the span → AWG_OUTSIDE_STANDARD_RANGE + formula_extrapolation
  • Missing/empty awg → MISSING_REQUIRED_INPUT (empty is not AWG 0 / 1/0)
  • Unparseable awg → INVALID_NUMBER; field not mm|mm2 → INVALID_MODE

Sources

Standards and references supporting this tool specification. Methods are listed separately — they are algorithms, not bibliographic sources.

Legacy published checks

Golden and boundary cases from the legacy Evidence JSON. CVP property, metamorphic, round-trip, O3, and interface statuses/checks are recorded in the Manifest — including SKIP when a suite has no vectors.

IDKindStatusDetail
awg-neg3-mmgoldenpassExpected 11.684 · Actual value=11.684 · unit=mm · gauge=4/0 · gauge_n=-3
awg-12-mmgoldenpassExpected 2.0525 · Actual value=2.0525253884939474 · unit=mm · gauge=12 · gauge_n=12
awg-12-mm2goldenpassExpected 3.3088 · Actual value=3.308772876111475 · unit=mm² · gauge=12 · gauge_n=12
awg-4-0-token-mmgoldenpassExpected 11.684 · Actual value=11.684 · unit=mm · gauge=4/0 · gauge_n=-3
awg-18-mmgoldenpassExpected 1.0237 · Actual value=1.0236873428326523 · unit=mm · gauge=18 · gauge_n=18
awg-18-mm2goldenpassExpected 0.823 · Actual value=0.8230468337313146 · unit=mm² · gauge=18 · gauge_n=18
awg-36-mmgoldenpassExpected 0.127 · Actual value=0.127 · unit=mm · gauge=36 · gauge_n=36
awg-36-mm2goldenpassExpected 0.0127 · Actual value=0.012667686977437443 · unit=mm² · gauge=36 · gauge_n=36
awg-0-mmgoldenpassExpected 8.2515 · Actual value=8.251462802171464 · unit=mm · gauge=1/0 · gauge_n=0
awg-10-mmgoldenpassExpected 2.5882 · Actual value=2.588186728012863 · unit=mm · gauge=10 · gauge_n=10
awg-40-mmgoldenpassExpected 0.0799 · Actual value=0.07987108513234509 · unit=mm · gauge=40 · gauge_n=40
awg-10-mm2goldenpassExpected 5.2612 · Actual value=5.261154954510371 · unit=mm² · gauge=10 · gauge_n=10
awg-alias-agoldenpassExpected 2.0525 · Actual value=2.0525253884939474 · unit=mm · gauge=12 · gauge_n=12
awg-missingboundarypassExpected MISSING_REQUIRED_INPUT · Actual MISSING_REQUIRED_INPUT
awg-emptyboundarypassExpected MISSING_REQUIRED_INPUT · Actual MISSING_REQUIRED_INPUT
awg-nanboundarypassExpected INVALID_NUMBER · Actual INVALID_NUMBER
awg-invalid-fieldboundarypassExpected INVALID_MODE · Actual INVALID_MODE
boundary-awg-1-0-tokenboundarypassExpected 8.2515 · Actual value=8.251462802171464 · unit=mm · gauge=1/0 · gauge_n=0
boundary-awg-12-5-finiteboundarypassExpected 1.937 · Actual value=1.9369203889327382 · unit=mm · gauge=12.5 · gauge_n=12.5
property-deterministicpropertypasssame AWG → same diameter
property-thicker-lower-awgpropertypassAWG10 diameter > AWG12
property-area-from-diameterpropertypassmm² = πd²/4
property-anchor-36propertypassAWG36 = 0.127 mm
property-thinner-higher-awgpropertypassAWG18 < AWG12
property-alias-apropertypasslegacy a ≡ awg
property-awg0-not-emptypropertypassAWG 0 (1/0) ≈ 8.25 mm
property-aught-4-0propertypass"4/0" ≡ −3
property-aught-1-0propertypass"1/0" ≡ 0
property-adjacent-diameter-ratiopropertypassd_n / d_{n+1} = 92^(1/39)
property-area-ratio-minus-3propertypassA_n / A_{n+3} ≈ 2
property-geometry-assurancepropertypassgeometry formula vs ASTM Table 1 vs copper resistance assurance layers
property-ampacity-assurancepropertypassampacity assurance = code_context_required
property-ampacity-12propertypassAWG 12 Cu thermal reference 20/25/30 A
property-ampacity-table-integritypropertypassAWG 14–4/0 Cu thermal reference table matches pinned 60/75/90 dataset
property-ampacity-18-not-tabulatedpropertypassAWG 18 has no 310.16-style ampacity row
property-iacs-resistivitypropertypasscopper resistivity is NBS Handbook 100 IACS 1.7241×10⁻⁸ Ω·m
property-ampacity-provenancepropertypassampacity provenance is educational NFPA 70 family, edition not pinned
property-extrapolation-warnpropertypassAWG 100 → formula_extrapolation + AWG_OUTSIDE_STANDARD_RANGE
property-extrapolation-assurancepropertypassAWG 100 geometry.assurance is formula_extrapolation without Table 1 nominal
property-nonstandard-gaugepropertypassAWG 12.5 → nonstandard_gauge interpolation, not outside-range
property-interpolation-assurancepropertypassAWG 12.5 geometry.assurance is formula_interpolation
property-geom-editionpropertypassgeometry source edition is ASTM B258-18(2026) reapproval (formula basis)
property-standard-nominal-12propertypassAWG 12 formula ≠ Table 1 SI nominal (2.0525… vs 2.052 mm)
property-standard-nominal-4-0propertypassAWG 4/0 Table 1 SI nominal 11.68 mm / 107.2 mm²
property-interpolation-no-nominalpropertypassAWG 12.5 has no ASTM Table 1 standard_nominal
property-monotonic-gridpropertypassdiameter decreases as AWG increases (−3…36)